LNG Equipment
Odorant Systems
Passing the Smell Test
Our Odorant System’s reservoir includes a liquid level transmitter and is always pressurized with vapor from the storage tank to ensure odorant pumps are primed and ready for operation.
The system features a mechanically adjustable discharge (from 0.25 to 3 cc) and can easily be configured in either a single or dual pump system. The odorant box assembly is designed with isolation valves so it can be separated from the rest of the system for easy maintenance.
Features
- Code-compliant, compact design with odorant reservoir and pump assembly on one frame
- Single or dual pump system configuration
- Always pressurized and ready for operation
Specifications
- Overall Dimensions(Standard Dual Pump System): 1’-9” X 5’-5” X 4’-9”
- Weight of Assembly: 500 lbs
- Design includes two main sub-components fabricated on one frame:
- (1) Odorant Reservoir
- (2) Odorant Pump Assembly (box enclosed)
- Easily configured in into a single or dual pump system
- Odorant system’s reservoir always pressurized with vapor from the storage tank to ensure odorant pumps are primed and ready for operation
- Odorant box assembly designed with isolation valves for ease of maintenance purposes
- Odorant pumps feature a mechanically adjustable discharge (from 0.25 to 3 cc)
- Odorant Pump: Williams Chemical Pump (Model: WIL P500V400CRTG)
- Design Code: ASME BPV Section VIII, Div. I (latest edition)
- MAWP: 100 PSI @ 100°F
- Design Temperature: -320°F to +100°F
- Odorant reservoir includes a liquid level transmitter
- Approximate Reservoir Volume: 14 gallons
- Odorant Filter: Williams Filter (Model: WIL F-12)
- Odorant Flow Switch: Ameritrol Inc. Flow switch (Model: IX-2575-D)